PARK DETROIT
19197 Sherwood Ave.
Detroit, MI 48234
Tel: (313) 366-2200
Fax: (313) 366-1540

Busways, Links to:
Low and Medium Voltage
Non-Segregated Phase Type | Segregated Phase Type | Features | Construction Options
Pictures 
| Specifications PDF Format | Installation Manual PDF Format (Large File)

Low Voltage Collector Bus
  Open Enclosure Type | Features | Pictures | Specifications PDF Format

Low Voltage (BD Style)
Plug-In Duct Data
| Duct Sections | End Cable Tap Boxes | Flanged Ends and End Closers
Selecting Elbows Tees & Crosses



Low Voltage (Low Reactance / Impedance Style)
Low Reactance Plug In Bus Duct
Low Impedance
Feeder Duct | Short Circuit Ratings | Selecting Elbows Tees and Crosses

BusWays
Low Reactance Plug In Bus Duct
COPPER BARS
Amperes
Phase Bars
Casing Dimension
Short Circuit *
800A
2-3/16 x 2
9 x 5-3/16
50,000
1000A
2-1/4 x 2
9 x 5-3/16
50,000
1350A
2-1/4 x 2-1/2
9 x 5-11/16
50,000
1600A
2-1/4 x 3
9 x 6-3/16
50,000
2000A
2-1/4 x 4
9 x 7-3/16
75,000
2500A
4-1/4 x 2-1/2
9 x 9-3/16
100,000
3000A
4-1/4 x 3
9 x 10-3/16
100,000
ALUMINUM BARS
Amperes
Phase Bars
Casing Dimension
Short Circuit
600A
2-3/16 x 2
9 x 5-3/16
50,000
800A
2-1/4 x 2
9 x 5-3/16
50,000
1000A
2-9/32 x 2-1/2
9 x 5-11/16
50,000
1350A
2-9/32 x 3-1/4
9 x 6-7/16
50,000
1600A
2-9/32 x 4
9 x 7-3/16
50,000
2000A
4-9/32 x 2-1/2
9 x 9-3/16
100,000

* These values are expressed in RMS symmetrical letthrough amperes on a six cycle basis. They can be slightly increased by the introduction of a fibre barrier at the scarf-lap joints. Consult the factory for higher values.
Voltage rating - 600 V or less AC or DC
Ventilated Steel Casing.
Conductors insulated in fluid be converted PVC.
Indoor use only.

M CONSTRUCTION COPPER BUS
(Copper bus bars based on a 1000A per square inch current density)
Amperes
Phase Bars
Casing Dimension
1000A
2-1/4 x 2
9 x 5-3/16
1350A
2-9/32 x 2-1/2
9 x 5-11/16
1600A
2-9/32 x 3
9 x 6-3/16
2000A
2-1/4 x 4
9 x 7-3/16
2500A
4-1/4 x 2-1/2
9 x 9-3/16
3000A
4-1/4 x 3
9 x 10-3/16

Busways, Links to:
Low and Medium Voltage
Non-Segregated Phase Type | Segregated Phase Type | Features | Construction Options
Pictures 
| Specifications PDF Format | Installation Manual PDF Format (Large File)

Low Voltage Collector Bus
  Open Enclosure Type | Features | Pictures | Specifications PDF Format

Low Voltage (BD Style)
Plug-In Duct Data
| Duct Sections | End Cable Tap Boxes | Flanged Ends and End Closers
Selecting Elbows Tees & Crosses



Low Voltage (Low Reactance / Impedance Style)
Low Reactance Plug In Bus Duct
Low Impedance
Feeder Duct | Short Circuit Ratings | Selecting Elbows Tees and Crosses

© Copyright Miller Media, Inc. 2000